Example project · Fire simulation
Fire development in an example hall
The fire moves along the lettering on the hall floor. Two minutes into the simulation, the west door and four roof smoke vents open.
Drag to rotate · Scroll to zoom
Loading the model …
Simulation time
75:00 min
≤ 20 °C180 °C≥ 350 °C
Monitoring point colours range from 20 to 350 °C.Results over 75 minutes
Results by time or position
Peak heat release rate1.25 MW
at 16:22 min
Peak gas temperature at the two points 2.0 m above floor102.0 °C
South-west point · 10:50 min
Peak gas temperature at the 16 roof points157.4 °C
Roof bay 2 / 3 · 4.4 m above floor · 27:10 min
Data and visualisation
Example hall · Scenario 2 · FDS 6.10.1. The 3D view shows 40 recorded states over 75 minutes. Heights are measured above finished floor level.
At each steel monitoring point, the chart shows the steel surface temperature and the adiabatic surface temperature (AST), a measure of thermal exposure.